Installation Services / 01b

Overhead LT Line

415 V distribution from the transformer to the load — bare LT lines, aerial bunched cable, street lighting circuits and service connections.

TRANSFORMER 415 V · 3-PHASE 4-WIRE NEUTRAL DISTRIBUTION BOX AB CABLE SERVICE CONNECTION NEUTRAL EARTH R · Y · B REBALANCED WHEN LOADS ARE ADDED

415 V, three phase and neutral, from the transformer LT side to the service connection. AB cable replaces bare conductor where the run passes close to buildings, and the neutral is earthed again at each distribution point — not only at the transformer.

The Work

LT overhead is the last stretch: transformer LT side to the distribution box, the shed, the pump or the pole light. It is the part of the network people actually touch, which is why insulation, clearance over roads and yards, and proper neutral earthing matter more here than anywhere else on the system.

Bare LT on cross-arms is cheaper to build; aerial bunched (AB) cable costs more and pays it back in fault rate, theft resistance and safety where the run passes close to buildings, trees or a public road. We will tell you which one the run actually wants rather than defaulting to whichever is quicker to string.

Scope Covered

  • Bare LT line on pin insulators and cross-arms
  • LT aerial bunched (AB) cable stringing and anchoring
  • Distribution boxes, feeder pillars and service connections
  • Street and yard lighting circuits with poles and fittings
  • Neutral earthing and pole earthing at every distribution point
  • Load balancing across phases and re-connection of existing services
415 V 3-phase 4-wire
240 V Single-phase service
AB Cable Where clearance is tight
Why It Matters

Where This Work
Decides The Outcome

This is the layer people can reach

LT lines run over yards, sheds, gates and footpaths. A low span or a broken tie on an LT run is a direct contact risk, not just an outage — which is why clearance and insulation get checked, not assumed.

Unbalanced phases burn the neutral

LT loads get added over years and rarely get re-balanced. The result is neutral current, overheating and voltage complaints at the far end. Balancing at the time of work costs nothing and prevents all three.

Earthing is what makes protection work

An LT fault only clears quickly if the earth path is sound. Neutral and body earthing at the transformer and at each distribution point is the reason a fuse blows instead of a frame staying live.

How We Execute

Survey To Handover

01

Load & route check

Connected load, phase balance and span conditions assessed to choose between bare LT and AB cable.

02

Erection

Poles, cross-arms, insulators or suspension clamps fitted; conductor or AB cable strung and anchored.

03

Distribution & services

Distribution boxes and feeder pillars mounted, service connections tapped and terminated.

04

Earth & energise

Neutral and pole earthing completed, insulation and earth resistance recorded, circuit energised and checked on load.